Question 1
A public fire hydrant has a rated capacity of 750 gpm at 20 psi residual pressure. Per NFPA 291, the bonnet and nozzle caps should be painted what color?
Show answer & explanation
Correct answer: D - Orange
10 free, exam-style Water-Based Systems Layout Level II (WBSL II) practice questions with answers and explanations. No signup required. Work through them below, then take the full free WBSL II practice test to study every exam domain.
These 10 free WBSL II questions are organized by exam domain, so you can see how each part of the Water-Based Systems Layout Level II blueprint is tested. Reveal the answer and explanation under each question.
A public fire hydrant has a rated capacity of 750 gpm at 20 psi residual pressure. Per NFPA 291, the bonnet and nozzle caps should be painted what color?
Correct answer: D - Orange
A developer is constructing a four-story apartment building, 52 ft in height above grade plane. Which NFPA standard is intended for the design of the sprinkler system in this residential occupancy?
Correct answer: C - NFPA 13R
A new data center requires automatic sprinkler protection, but the owner is concerned about water damage to servers caused by accidental discharge or a single physically broken sprinkler. Which system type BEST addresses this concern?
Correct answer: B - Pre-action system
Per NFPA 13, the maximum protection area for a single standard-spray pendent sprinkler in a Light Hazard occupancy with unobstructed, noncombustible construction is:
Correct answer: C - 225 ft²
A warehouse stores noncombustible metal automotive parts in single-layer corrugated cartons placed directly on wooden pallets. Under NFPA 13, this commodity is classified as:
Correct answer: A - Class I
A sway brace is required to resist horizontal seismic forces acting parallel to (along the length of) a feed main. Which type of brace is this?
Correct answer: C - Longitudinal sway brace
A building is equipped with a standpipe system that provides only 2½-in. hose connections intended for use by the fire department and trained personnel. Per NFPA 14, this system is classified as a:
Correct answer: B - Class I standpipe
Per NFPA 20, when a centrifugal fire pump is operating at 150% of its rated capacity, the net pressure it delivers must be NOT LESS THAN what percentage of its rated pressure?
Correct answer: B - 65%
A standard pendent sprinkler has a K-factor of 5.6 and is flowing at a pressure of 25 psi. Using Q = K√P, what is the discharge in gpm?
Correct answer: D - 28.0 gpm
A sprinkler is located 25 ft above the system riser. Approximately how much pressure is required to overcome this elevation?
Correct answer: A - 10.8 psi